Low power transformer

Low-power transformers include single-phase transformers with an output power of 4 kVA and below, three-phase transformers with a power of 5 kVA and below. These transformers are used in radio engineering, electronics, automation, communications, industrial electric drive devices to reduce the voltage in working circuits in order to ensure their safe operation, as well as to power household electrical appliances, etc. The range of these transformers is extremely diverse.

The tables show the characteristics and parameters of widely used low-power transformers supplied by order and designed to supply control circuits of electric drives and other electrical consumers, local lighting lamps, low-voltage signaling circuits and rectifiers assembled in a full-wave circuit (see Figure 1). These transformers are manufactured in accordance with GOST 16710-76 and have a type designation OSM - single-phase, dry, multipurpose... Their climatic design in accordance with GOST 15150-69 is designated: for a temperate climate - UZ (ambient temperature from -45 to +40 ° C), tropical-resistant - TZ (from -10 to +45 ° C) and cold-resistant - HLZ (from -60 up to +40 ° С). The design, electrical parameters, overall and installation dimensions are the same for all three transformers. The permissible overvoltage for the supply network is not more than 10 %, for the load current - not more than 5 % while maintaining the power not exceeding the nominal.

Fig. 1 a - for power supply of control circuits, signaling and local lighting; b -

for power supply of rectifiers of control circuits; c - to work in dynamic braking circuits

Vibration of the transformer attachment points with a frequency of up to 60 Hz and an acceleration of no more than 10 m / s2 is also permissible.

Rated primary voltages of transformers of type OSM - 220, 380 and 660 V, secondary - in accordance with tables 1-4. A combination of any of the indicated primary voltages with any (any with two secondary windings) of the secondary is possible. No-load currents and short-circuit voltages are determined according to table 5, overall dimensions and weights - according to Fig. 2 and table 6

Fig. 2 Overall and installation dimensions
transformers 

type OSM   
 

Table 1 Parameters of transformers intended for power supply of control circuits, signaling and local lighting (see 1 a) 

Transformer

Rated power of the transformer kVA

Rated power of secondary control windings kVA

Rated power of secondary lighting windings, kVA

Rated voltage of secondary windings  control, V

Rated voltage of secondary lighting windings, V

OSM-0.1

0,1

0.075

0,25

110,120

12,24,36,42,110

OSM-0.16

0,16

0,1

0,060

110,120

12,24,36,42,110

OSM-0.25

0,25

0,19

0,060

110,120

12,24,36,42,110

OSM-0.4

0,4

0,34

0,060

110,120

12,24,36,42,110

OSM-0.63

0,63

0,51

0,120

110,120

12,24,36,42,110

OSM-1.0

1,0

0,88

0,120

110,120

12,24,36,42,110

 

 

Table 2 Parameters transformers designed to power rectifiers of control circuits (see Fig. 1 b)  

Transformer

Rated power kVA

Rated voltage of the secondary winding, V

Secondary winding voltage after rectification, V

OSM-0.063

0.63

14,29,56,130,260

12,24,48,110,220

OSM-0.1

0.1

14,29,56,130,260

12,24,48,110,220

OSM-0.16

0.16

14,29,56,130,260

12,24,48,110,220

OSM-0.25

0,25

14,29,56,130,260

12,24,48,110,220

OSM-0.4

0,4

14,29,56,130,260

12,24,48,110,220

 

 Tab. 3 Parameters of transformers designed to supply local lighting circuits or control circuits (see Fig. 1 b)

 

Transformer

Rated power kVA

Rated voltage of the secondary winding, V

OSM-0.063

0.63

12,24,36,42,110,220

OSM-0.1

0.1

         12,24,36,42,110,220

OSM-0.16

0.16

         12,24,36,42,110,220

OSM-0.25

0,25

         12,24,36,42,110,220

OSM-0.4

0,4

         12,24,36,42,110,220

OSM-0.63

0.63

110,220

OSM-1.0

1.0

                    110,220

Tab. 4 Parameters of transformers designed to work on dynamic braking circuits (see fig. 1 c)

Transformer

Rated power of the transformer, kVA

Rated power of secondary windings, kVA (2 and 3)

Rated voltage of secondary windings (2 and 3), V

OSM-0.063

0.63

0,0315

14,29,56,82

OSM-0.1

0.1

0,05

14,29,56,82

OSM-0.16

0.16

0,08

14,29,56,82

OSM-0.25

0,25

0,125

14,29,56,82

OSM-0.4

0,4

0,2

14,29,56,82

OSM-0.63

0.63

0,315

14,29,56,82

OSM-1.0

1.0

0,5

14,29,56,82

 Table 5 Parameters of transformers of the OSM type

Transformer

Idle current, %

Short circuit voltage

OSM-0.063

24

12,0

OSM-0.1

24

9,0

OSM-0.16

23

7,0

OSM-0.25

22

5,5

OSM-0.4

20

4,5

OSM-0.63

19

3,5

OSM-1.0

18

2,5

 Table 6 Overall dimensions, (mm) and weight of OSM type transformers  (see fig. 2) 

Transformer

A

V

H

L1

L2

d

Weight, kg

OSM-0.063

84

115

95

52

58

5,5

1,4

OSM-0.1

100

120

95

52

73

5,5

2,0

OSM-0.16

110

140

115

70

83

5,5

3,0

OSM-0.25

124

145

132

70

90

5,5

4,3

OSM-0.4

124

170

140

92

93

6,5

6,2

OSM-0.63

135

210

185

123

92

6,5

9,5

OSM-1.0

165

210

185

123

128

6,5

14,4

To the list of articles